LG1093AC05 | Honeywell | LG1093 Flame Detector
Overview: The Honeywell LG/EG flame monitoring system is designed to detect UV radiation emitted by hydrocarbon flames, providing reliable flame detection and indicating flame or no-flame conditions. This sensor has demonstrated proven performance on General Electric (GE) and GE licensee gas turbines for over 35 years. Features: Sensor Technology: Utilizes a Geiger-Mueller type sensor phototube that detects UV radiation in the 180-260 nm spectrum. It is solar blind and tolerant to black body radiation. Response Times: Flame Present Response Time: 0.1 seconds (typical) Flame Loss Response Time: 0.2 seconds (maximum) Temperature Range: Operates effectively in temperatures from -40°C to 176°C. Operating Distance: Effective up to 330 meters (1000 feet) from sensor to amplifier. Hardware Outputs: Compatible with EG1033 amplifier modules: EG1033AA: Transistor open collector EG1033AB and EG1033AC: Relay contacts (SPDT) Amplifier Voltage Support: 28 VDC 20-35 VDC 1