Gamewell FCI AMM-2 Mini Monitor Module
The Addressable Monitor Module AMM-2 features a single Style B, Class B initiating circuit with end of line resistor. This module provides an address for any device or group of devices connected to this circuit. Any alarm initiating devices with normally open (N.O.) dry contacts, such as heat detectors, linear heat detection devices, projected beam smoke detectors, 4-wire smoke detectors, water flow switches, tamper switches, manual stations, etc. may be installed in this circuit. The AMM-2 module is designed for installation in the signaling line circuit of any FCI analog addressable control panel. The signaling line circuits of FCI analog addressable panels are designed to accommodate up to 99 monitor modules per circuit. The initiating circuit of the AMM-2 has a maximum line resistance of 1,200 ohms, allowing the module to accommodate a substantial number of initiating devices located at considerable distances from the module. The compact size facilitates the installation of the mod